تحسين الفولتية وتقليل خسائر منظومة الشبكة العراقية باستخدام افضل جهاز FACTs == Improvement of Voltage Profile And Reduce Iraqi Grid System Losses By Using Optimal FACTs Device
Author name:
سيف اسعد عبد الحسين
Supervisor name:
رشيد حميد الربيعي | انعام ابراهيم علي
General topic:
Electrical, Electronic and Communications Engineering
Specific topic:
Electrical Engineering
Degree:
Master
University:
University of Technology - Electrical Engineering Department - Electrical Engineering Branch
Language:
English
University location:
Baghdad
First pages:
34T511 - p.pdf
Abstract:
الغرض من هذا العمل هو تحسين الجهد والتقليل من خسائرالقدرة للشبكة العراقية ( 400kV ) عن طريق تركيب اجهزة ( FACTs ) في مواقع مختلفة تحت حالة خطا ومقارنة النتائج مع تلك دون وجود (FACTs) تحت نفس الظروف.تم تحديد الموقع الامثل للـ(FACTs) على اساس الخوارزميات | The aim of this work is to improve the voltage profile and reduces power losses of Iraqi (400kV) power grid system by installing Flexible Alternating Current Transmission System devices (FACTs).The optimal location of the FACTs device was specified based on Genetic Algorithm (GA) optimization method and power system analysis toolbox ( PSAT) package, it was utilized to search for optimum FACT parameters setting and location based objective function that depends on the power and voltage as fitness.MATLAB (R2011a) was used for running both GA program and Power System Analysis Toolbox (PSAT) version 2.1.6, Newton Raphson method also used for solving the load flow of the system and the Trapezoidal method for the non - linear differential equations.Two systems have been implemented in this work as follows; • IEEE - machine 9 - bus system.• INSGS 11 - machine 24 - bus, 39(400kV) overhead transmission line.The GA program is implemented on IEEE 9 - bus system, then after getting the appropriate results the same procedure repeated for the Iraqi grid system which is more complicated, its used to find the optimal location of Unified Power Flow Controller (UPFC). The results obtained from GA have been compared with PSAT and showed that the installation of (UPFC) devices at the optimal locations of the Iraqi grid gives an improvement in the power losses and voltage after subjected to the three phase fault to ground at different locations and different cases (temporary fault, permanent fault).